 1 Phase 60 W CliQ

Features

  • Ease of wire connection to terminals
  • Compact design for easy handling
  • Overload protection
  • Overvoltage protection
  • Thermal protection
  • Power boost 150% for 3 seconds
  • Expected life time: 10 years
  • Redundancy: Yes (with external oring diode)
  • RoHS compliant


The product offers a nominal output voltage of 24 V, a wide temperature range from -20°C to +75°C and a minimum holdup time of 20 ms.
The 60 watts CliQ DIN Rail power supply provides overvoltage, overload and thermal protection.
Due to the wide input voltage range from 85 to 264 Vac, the Delta's CliQ power supply is worldwide usable. Multiple output terminals for fast wiring and easy installation. 
   

The CliQ DRP024V060W1AZ is RoHS compliant.

 

 

 Input Specifications    Output Specifications  
 Input voltage range (Vac)

 85 - 264 (DC input range
 120 - 375 Vdc)

 Output power (W)  60
 Input frequency (Hz)  47 - 63  Output voltage range (V)  22 - 28
 Nominal current (A)  1.1 @ 115 Vac, 0.7
 @ 230 Vac
 Output currentt (A)  2.5
 Inrush current limitation (A)
  l²t (+25°C) typ.
 30@ 115 Vac, 60
 @ 230 Vac typ.

 Residual ripple /
 peak switching

 (20 MHz) (at nominal values)

 < 50 mV / < 240 mVpp
 Power factor  Conform to
 EN 61000-3-2 STD
 Mains buffering at
 nominal load (typ.)
 > 20 ms@115 Vac,
 > 125 ms@ 230 Vac
 Efficiency (%)  > 85% typ.  Line regulation  0.5% typ. (@ 85 - 264 Vac 
 input, 100% load)
 Leakage current  < 1 mA  Load regulation

 < 1% typ.
 (with rated input, 0 100% load)

       
 Environmental    Mechanical design  
 Operating ambient
  temperature (°C)
 -20 ... +75 *  Case cover  Plastic (PC)
 Storage temperature (°C)

 -25 ... +85

 Dimensions (L x W x H)  120.6 mm x 32 mm x 113 mm
 Humidity operation (%)  < 95  Unit weight / box  0.325 kg
     MTBF  > 800,000 hrs
 Note (*)  * Operating amb.
 < 0°C to -20°C
 derate power by 1% /°C
 Noise  Sound pressure level(SPL)
 < 40dBA
   * Operating amb. > 50°C
 derate power by 2.5% / °C
 Cooling  Convection
   * Operating amb. > 70°C
 derate power by 4% / °C
 Input terminal  M4 x 3
     Output terminal  M4 x 2
     Mounting rail  Standard TS35 mounting rail
     Shock proof  IEC 60068-2-27
     Vibration  IEC 60068-2-6
     Protection structure  EN 60950 meet IPX0
 
   
 Safety      
 EMC / Emissions  Class B / EN55022  Voltage dips  Conform to EN 61000-4-11
   CISPR22, Class B  Galvanic isolation  Input to output: 4 KVac
   FCC Title 47    Input to ground: 1.5 KVac
   EN 61204-3 (Class B on AC
 & Class A on DC side)
   Output to ground: 1.5 KVac
 Immunity  EN 61000-4-2, 1995  Approvals  UL508
   EN 61000-4-3, 1998    EN 60950
   EN 61000-4-4, 1995    cULus 60950
   IEC 61000-4-5, 1995    EN 50178
   EN 61000-4-6, 1996    EN 60204
   EN 61000-4-8 or
 IEC 61000-4-12 or
 IEEE C62.41
   GS
   EN 61000-3-2, 1994    CCSAus to CSA C22.2
 No. 60950-1: 03
     

 

 