60 W 1-Phase CliQ Power Supply
Products
 60 W, 12 V CliQ

Features

  • Ease of wire connection to terminals
  • Compact design for easy handling
  • Overload protection
  • Overvoltage protection
  • Thermal protection
  • Power boost 150% for 3 seconds
  • Expected life time: 10 years
  • Redundancy: Yes (with external ORing diode)
  • RoHS compliant


 

 

 Input Specifications    Output Specifications  
 Input voltage range (Vac)

 85 - 264 (DC input range
 120 - 375 Vdc)

 Output voltage (V)  12
 Input frequency (Hz)  47 - 63  Output voltage range (V)  11 - 14
 Nominal current (A)

1.35 @ 115 Vac,
 0.8 @ 230 Vac

 Output currentt (A)  5.0
 Inrush current limitation (A) 
 l²t (+25°C) typ.
 <50@ 115 Vac,
 <100 @ 230 Vac

 Output power W

 60
 Power factor  Conform to
 EN 61000-3-2 STD

 Residual ripple /
 peak switching

 (20 MHz)

 < 100 mV
 Efficiency (%)  85.5%min. @ 115/
 230 Vac
 Mains buffering at
 nominal load (typ.)
 > 22 ms@115 Vac,
 > 110 ms@ 230 Vac
 Leakage current  < 1 mA  Line regulation  0.5% typ. (@ 85 - 264 Vac
 input, 100% load)
     Load regulation

 < 1% typ.  (with rated input,
 0 - 100% load)

 Environmental    Mechanical design  
 Operating ambient
 temperature (°C)
 -20 ... +75 *  Case cover  Aluminium (Al5052)
 Storage temperature (°C)

 -25 ... +85

 Dimensions (L x W x H)  121 mm x 32 mm x 120 mm
 Operating humidity (%)  < 95 RH  Unit weight / box  0.325 kg
     MTBF  > 300,000 hrs
   *Operating amb. > 50 C
 derate power by 2.5%/C;
  Operating amb. > 70 C
 derate power by 4%/C
 (Only for 15,30 & 60W)
 Noise  Sound pressure level(SPL)
 < 40 dBA
     Cooling  Convection
     Input terminal  M4 x 3
     Output terminal  M4 x 2
     Mounting rail  Standard TS35 mounting rail
     Shock proof  IEC 60068-2-27
     Vibration  IEC 60068-2-6
     Protection structure  EN 60950 meet IPX0
 
   
 Safety      
 EMC / Emissions  Class B / EN55022  Voltage dips  Conform to EN 61000-4-11
   CISPR22  Galvanic isolation  Input to output: 4 KVac
   CISPR11, Class B    Input to ground: 1.5 KVac
   FCC Title 47    Output to ground: 1.5 KVac
 Immunity  EN55024,EN61000-6-1,-2  Safety standard
       UL/cUL Listed to UL508 and
 CSA C22.2 no.107.1-01,
 UR/cUR recognize to
 UL60950-1 and CSA C22.2
 No. 60950-1, TUV-Bauart
 Mark to EN60950-1, EN50178:
 1998, IEC62103: 2003, CB
 test certificate and report to
 IEC60950-1,CCSAus to CSA
 C22.2 No. 60950-1,
 UL 60950-1 and CSA C22.2
 No. 107.1-01,CE (EMC and
 Low Voltage directive) and
 CCC (prepared)
       

Username: 
Password: 

Search:  
 
printversionPrintversion

Related
Documents
 Catalogue_CliQ_PanelMount_en
  » Catalogue_CliQ_PanelMount_en - 8528 Kb 
 Catalogue_CliQ_PanelMount_fr
  » Catalogue_CliQ_PanelMount_fr - 8531 Kb 
 Tech.Info-CliQ_60W_1P_12V
  » Tech.Info-CliQ_60W_1P_12V - 851 Kb 
backtop of page
© 2010 Delta Energy Systems